A Coordinated Source-Grid Control Strategy for Wind Farm Integration With VSC-HVDC and Transmission With LCC-HVDC
ZENG Xueyang,LIU Tianqi,WANG Shunliang,LI Baohong,LI Xingyuan,ZENG Qi,CHEN Xiang
DOI: https://doi.org/10.13335/j.1000-3673.pst.2017.0144
2017-01-01
Abstract:To solve frequency-sensitive variance of sending end power grid (SEPG),caused by technical solution of wind farm integrated with voltage sourced converter based HVDC (VSC-HVDC) and transmitted with line commuted converter based HVDC (LCC-HVDC) in plateau area of Western China,a coordinated source-grid control strategy is proposed.In this strategy,LCC-HVDC,VSC-HVDC and wind farm participate in SEPG frequency regulation.Firstly,considering primary frequency control and inertia response control,variable power supplementary control is implemented in LCC-HVDC and wind turbines,and variable voltage supplementary control is implemented in grid side VSC.Variable frequency control and DC voltage marginal supplementary control are implemented in wind farm VSC.Secondly,timing sequence of frequency regulation,in which generators,LCC-HVDC,VSC-HVDC and wind farm participate,is coordinated in SEPG.Finally,a simulation model is set up in PSCAD/EMTDC.Simulation results show that the coordinated source-grid control strategy can improve inertia time constants and SEPG frequency stability,and effectively reduce DC voltage fluctuation amplitude of VSC-HVDC when fault occurs in SEPG.