Strategy Design of Frequency Limit Controller on Multi-HVDC Asynchronous Interconnected Power System

GAO Qin,CHEN Yiping,ZHU Lin,ZHANG Yong,TANG Zhuoyao,LI Chongtao
DOI: https://doi.org/10.7500/AEPS20170911003
2018-01-01
Abstract:Yunnan power grid asynchronously interconnects with the main grid of China Southern Power Grid by multiple high voltage direct current(HVDC)transmission systems,and the frequency limit controller(FLC)plays a significant role in the frequency control of sending-side system.In the HVDC single-polar block experiment,which is called Chuhui DC system, some HVDC transmission lines operate in an overloaded mode for a long time because of the mismatching between FLC and primary frequency control(FPC).By analyzing the dynamic regulation process of the FLC,regulatory characteristics of different models of the FLC and the coordinated cooperation relationship with primary frequency regulation are clarified.On the basis of that,the paper analyzes the influence of FLC reserve capacity,dead band on the frequency peak and releasing process of FLC by time domain simulation and a frequency modulation strategy of FLC is proposed.Furthermore,the governor parameters are redesigned by eigenvalue sensitivity method for improving the dynamic performance of FPC,which can make the best of FLC on frequency peak restriction and cooperate with primary frequency regulation in the meanwhile to guarantee the rapid release of its adj ustment.The results of operation show the availability of proposed strategies.
What problem does this paper attempt to address?