The Effect of Liquid Charge Ratio on Organic Rankine Cycle Operation

Shuang Cao,Zheng Miao,Jinliang Xu
DOI: https://doi.org/10.1016/j.applthermaleng.2019.114227
IF: 6.4
2019-01-01
Applied Thermal Engineering
Abstract:Liquid charge ratio is defined as the total liquid volume charged in an organic Rankine cycle (ORC) system divided by the total internal volume of the system, which influences the two-phase (vapor-liquid) phase distribution to dominate the component operation. In this paper, the effect of liquid charge ratio on ORC performance is explored for a similar to 10 kWe ORC system. It is shown that ORC can operate with liquid charge ratios in the range of 35-50%. At an optimal liquid charge ratio of 42.5%, the system attains the maximum thermal efficiency, power efficiency and net efficiency of 7.74%, 7.02% and 5.62%, respectively. When the system operates below the optimal liquid charge ratio of 42.5%, the liquid flushing may occur to induce pump cavitation and unstable flow due to insufficient liquid suction during pumping process. Alternatively, when the system operates above the optimal liquid charge ratio of 42.5%, more liquid is occupied in the condenser, decreasing the effective heat transfer area to elevate the condensation pressure, thus the system efficiency is worsened. This paper presents the important criterion for optimal liquid charge ratio for ORC operation.