Microgrid Inverter Parallel Operation Strategy in Large Feeder Impedance Environment

WANG Yichao,LUO An,JIN Guobin,MA Fujun
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2015.04.012
2015-01-01
Abstract:With the increasing size of the isolated microgrid, more and more inverters access to microgrid through LCL filters or coupling transformers, which make the inverters have large inductive feeder impedance or reveal large feeder impedance difference. In the large feeder impedance environment, adjusting the output impedance of inverter by conventional virtual impedance strategy will increase voltage drop on feeder impedance, worsen power quality of microgrid under the nonlinear load conditions and make good current-sharing control difficult. Therefore, a control method, which can directly control the voltage at the installation point, was proposed for inverter parallel operation. By directly controlling the voltage at the installation point, the feeder impedance on grid side was converted into the equivalent output impedance of the inverter itself. With the use of the quasi-proportional resonant controller, the amplitude of equivalent output impedance of the inverter itself was reduced, thus, a big feeder impedance problem was converted into a small feeder impedance problem, and which will weaken the adverse effects of feeder impedance on grid side on circulation suppression and microgrid voltage. In the small feeder impedance environment, the resistive virtual impedance strategy and the droop control strategy were applied to realize accurate power sharing and circulation suppression. Simulation and experimental results show the correctness and validity of the proposed control method.
What problem does this paper attempt to address?