Adaptability Analysis of Fault Component Protection of Power Systems With Wind Farms

WANG Chenqing,SONG Guobing,LIU Kai,WANG Donghui,KANG Xiaoning,JIAO Zaibin
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2014.31.004
2014-01-01
Abstract:Fault component protection is widely applied in traditional power systems, thus it is worthy of deep research for the adaptability of fault component protection to power systems with wind farms. So the protection criterion based on fault components were analyzed theoretically to get the most suitable working condition of this protection. Under this working condition, the fault feature of power systems with wind farms were studied by combining field fault recording data and simulation. The adaptability of fault component protection of power systems with wind farms was researched. The research results show that fault component protection works well only when the positive sequence impedance at back system keeps stable, or the positive sequence impedance at back system is equal to the negative sequence one. While when fault occurs in wind power systems, the positive sequence impedance at wind farm side has large fluctuations and is obviously different from the negative sequence one, and this makes the protection work in unfavorable conditions and significantly reduces the reliability of the protection based on fault component. When the fault component protection is applied to power systems with wind farms, it should be set conservatively at the cost of sensitivity.
What problem does this paper attempt to address?