Research on Active Response Policy for Grid Friendly Air Conditioning Load

ZHANG Zhidan,HUANG Xiaoqing,CAO Yijia,TIAN Shiming,LIU Jidong,PENG Hanmei
DOI: https://doi.org/10.13334/j.0258-8013.pcsee.2014.25.002
2014-01-01
Abstract:Rapid growth of air conditioning has caused large effect on safe and economical operation of power grid. Based on “Grid Friendly” technology, this paper proposes active response policy for air conditioning load. Fundamentals and implementation scheme of the policy are discussed particularly. The core idea of the policy is that the air conditioning equipment adjusts operation state automatically according to the change of grid voltage, which can relieve the adverse effect on the stable operation of power system. Typical distribution network example and aggregation model for air conditioning load fit for transient stability study are set up to verify the proposed three active response policies. The simulation results show that the hierarchical distributed active response policy for air conditioning is able to prevent large fluctuation of grid voltage as well as avoid the impact on power grid when air conditioning equipments respond actively. Active response for grid friendly air conditioning load is beneficial to maintain the safe and stable operation of power grid, which also provides a certain reference for realizing friendly interaction between power consumers and distribution network.
What problem does this paper attempt to address?