Coordinated Control Method of Interconnected Grid to Solve Cascading Faults of UHVDC Valve Groups

WU Ping,ZHAO Bing,GUO Jianbo,BU Guangquan,LI Yong,LIU Changyi,XU Youping,JIANG Guoqing,XI Jianghui,HU Yangyu,SHAO Dejun
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.2436
2017-01-01
Abstract:Recently,UHVDC control and protection system based on pole level was already canceled.Now configuration of UHVDC block fault is cascading failures of valve groups.However,traditional coordinated control could only be executed once in one second.As a result,DC fast power support capacity cannot be fully played.To solve cascading faults of UHVDC converters in short time,a coordinated control method modulating DC power after certain time was proposed.By optimizing DC power emergency control timing,DC could fully play replacement role of load shedding measures,solving the problem of too large load-shedding quantity due to constraint of DC power adjustment ability.The method is already applied to AC-DC coordinated control system in Central-China power grid.