Impacting Factors and Stable Area Analysis of Subsynchronous Resonance in DFIG Based Wind Farms Connected to Series-Compensated Power System

DONG Xiaoliang,XIE Xiaorong,YANG Yu,HAN Yingduo
DOI: https://doi.org/10.13335/j.1000-3673.pst.2015.01.029
2015-01-01
Abstract:Taking a certain doubly fed induction generators (DFIG) based wind farm located at North China, which is connected to the series-compensated power transmission system, as the prototype, firstly, through the eigenvalue sensitivity analysis the predominant factors influencing the subsynchronous resonance (SSR) of wind turbine are obtained; then the stability of the whole operating area of wind turbines, in which the maximum power point tracking (MPPT) is included, is researched to explain the influences of the change of various predominant factors on DFIG stability and secure operation area. Research results show that under the same conditions the higher the series compensation degree, the higher the risk of leading to SSR is and the small the stable area will be. The proportional gain if the current loop in rotor side converter of the wind turbine itself plays the role of negative damping, decreasing the gain may play a certain role to suppress SSR, the smaller this gain the larger the stable area will be. It is also found that under a certain condition decreasing the number of DFIG can eliminate the risk of occurring SSR and the SSR frequency varies with the number of DFIG. On this basis, some suggestions on the setting of DFIG control parameters and secure operation of wind farm are given.