Online monitoring of excitation winding inter-turn short circuit of generator/motor

Yuguang SUN,Binghui WANG,Wei XU,Chengsheng JIANG
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.03.033
2017-01-01
Abstract:As the general schemes of online excitation winding inter-turn short circuit monitoring take all the fractional harmonic components of imbalanced stator neutral-point current as the monitoring variables to form the corresponding alarm threshold,they are not sensitive enough to the short circuit across a few turns due to the higher alarm threshold.With the generator/motor of Yixing pumped storage power station as an example,the imbalanced stator neutral-point current caused by the short circuit across a few turns of excitation winding is calculated,the inherent imbalanced stator neutral-point current in normal operating condition is measured,and an improved online monitoring scheme is proposed,which only adopts bigger harmonic components,i.e.three-eighths and five-eighths harmonic components,to form the alarm threshold.Simulative results show that,with higher sensitivity than the general schemes,the improved scheme issues alarm for the excitation winding inter-turn short circuit of 3 % turn-ratio and above.The online monitoring equipment based on the improved scheme for generator/motor No.4 of Yixing pumped storage power station has been successfully put into operation.