Comparative test of effective height of UHF sensor for partial discharge in GIS

SHU Shengwen,CHEN Jinxiang,CHEN Bin,YE Zhaoping,CHEN Minwei,YOU Hao
DOI: https://doi.org/10.16081/j.issn.1006-6047.2017.07.025
2017-01-01
Abstract:The coupling performance of UHF (Ultra-High Frequency) sensor has to be checked to improve the site application effectiveness of UHF detection technology for partial discharge in GIS(Gas Insulated Switchgear).A test platform based on the GTEM(Gigahertz Transverse ElectroMagnetic) cell is built to test the effective height of UHF sensor.The average effective height within 0.3~1.5 GHz and the percentage of effective height above 2 mm are adopted to characterize the coupling performance of UHF sensor.Based on the GTEM750 cell,the time-domain pulse method and sweep-frequency reference method are applied to comparatively test the effective height of UHF sensor.The test results are compared between GTEM750 cell and GTEM1500 cell.Based on the GTEM750 cell and the time-domain pulse reference method,the influences of sensor type,installation mode and installation angle on the tested effective height of UHF sensor are discussed.Research results show that,the deviation of average effective height within 0.3~1.5 GHz between different platforms or methods is within ±1 mm;the sensor type,installation mode and installation angle have obvious influences on the average effective height.
What problem does this paper attempt to address?