Study on Pollution Flashover Characteristics of RTV Coating Disc Suspension Insulators with Different Local Defects

Xiangyun FU,Bin CAO,Jiansheng CUI,Haoran SUN,Hongwei MEI,Liming WANG
DOI: https://doi.org/10.13296/j.1001-1609.hva.2018.08.005
2018-01-01
Abstract:Under high temperature, high humidity and strong ultraviolet radiation environment, the performances of RTV (room temperature vulcanized silicone rubber) coating caused by pulverization, local defect and uneven hydrophobicity on surfaces of insulator will be deteriorated. In this paper, the effects of anti-pollution flashover of RTV with partial defects are analyzed. The pollution flashover tests of glass samples with RTV coating are designed to research the influence of the pollution flashover voltage and the similar cap and pin insulators are also used to verify the test results. The finite element software is used to analyze the influence of the electric field on the surface of insulator caused by local defects. The test results show that the anti-pollution flash performance will become much worse as the length of partial defect of RTV coating in the direction of creepage distance is longer, the influence of pollution flashover voltage is different if the position that the partial defect of RTV coating on the surface of insulator is located in different, and there is no significant decrease in the anti-pollution flashover performance if the partial defect appears on the high voltage side. The electric field in other area of RTV coating will enhance, which leads to the corona discharge more likely to appear and damage the hydrophobicity of other RTV coating.
What problem does this paper attempt to address?