Analysis on Disturbance Characteristics of HVDC Based on Actual Engineering Control System——Disturbance Characteristics of Rectifier Side and Its Optimization

Chao ZHENG,Chao HUO,Shibin BAI,Sizhuo L(U),Huiling LI,Xin ZHANG
DOI: https://doi.org/10.13336/j.1003-6520.hve.20171227037
2018-01-01
Abstract:In order to reduce the voltage fluctuation caused by HVDC disturbance,and enhance the safety of grid connected wind turbines,on the basis of the control system simulation model of HVDC aiming to the practical engineering which was newly developed in PSD-BPA power system electromechanical transient simulation software,we analyzed the dynamic response characteristics of the main electric quantity of the HVDC system under the AC voltage disturbance at the rectifier side.Then we evaluated the effects of different AC voltage disturbance characteristics and HVDC controller parameters on the response characteristics,revealed the mechanism of overvoltage threat because of the reactive surplus of rectifier station,and put forward the relevant optimization measures.For the multi-HVDC transmission system,it was verified that the disturbance characteristics can be improved and the security can be increased by decreasing the magnitude of RAML,increasing the gain coefficient of current controller,and decreasing the boot threshold of VDCOL.
What problem does this paper attempt to address?