Dielectric Recovery Process of Multiple Re-ignition Phenomena After Small Inductive Current Interruption in Vacuum

Feng WANG,Zhongyi WANG,Mengmeng HAO,Zhiyuan LIU
DOI: https://doi.org/10.13336/j.1003-6520.hve.20180529039
2018-01-01
Abstract:Multiple re-ignition overvoltage is determined by dielectric recovery strength after interruption of small inductive currents in vacuum. We established a micro-physical model for small inductive current interruption in vacuum, with which the influence of load parameters on the re-ignitions can be determined, so as to reveal the sheath development process after interruption of small inductive current in vacuum. The following micro-parameters were determined, including the ion density, ion speed, development of electric field, and potential distribution under various TRVs. A critical electric field strength at the cathode was chosen as a criterion for the re-ignition. The simulation results show the following influence of load parameters on the re-ignitions of small current inductive current interruption in vacuum. A higher load capacitance or a higher load inductance will decrease the sheath development speed and the maximum field strength, which decreases the overvoltage and the risk of re-ignition. The sheath speed and the maximum field strength does not change with the increase of the equivalent resistance, but the load current decreases with the increase of the equivalent resistance. A lower load current reduces sheath velocity, which results in a lower maximum electric field strength. Therefore, it decreases the risk of re-ignition.
What problem does this paper attempt to address?