Abstract:Rotational inertia of control strategy of traditional virtual synchronous generator (VSG) is constant in the ontology model,which may produce power oscillation and deviation of the grid-connected inverter as it approaches to a steady state.Therefore,the paper presents a kind of improved control strategy for VSG.This strategy adopts band-pass damping factor to replace constant damping factor in the traditional ontology model,which makes the grid-connected inverter rapidly get into a steady state when deviation of the power grid frequency and rotational frequency is small.Compared with traditional constant damping factor,band-pass damping factor can not only suppress power oscillation but also have no effect on output active power of VSG.Based on MATLAB/Simulink,the paper verifies this control strategy and the result indicates the strategy is in normal performance under off-grid mode or grid-connection mode,which shows it can meet requirement of electric power quality.