Investigation of Energy Usage in the University Buildings

M. A. Salam,M G Yazdani,Fushuan Wen,Q. M. Rahman,M. Rakib Uddin,A J Christina,Amir
DOI: https://doi.org/10.1049/cp.2018.1593
2018-01-01
Abstract:This paper presents the investigation on electrical energy usage in two academic blocks, A and F in the Universiti Teknologi Brunei. The energy usage has been measured for a period of seven months with energy meters located in the switchboard. From the measured data, it has been found that 69% of the electrical energy is consumed by air-conditioning system while the other 31% is consumed by the lighting systems and miscellaneous sockets. From the connected load, it has been found that the air-conditioning equipment in block F is not fully utilized whereas in block A, it is fully utilized. The lighting intensity requirement for both the blocks are found to comply with the standard values. The connected air-conditioning loads per person has been found to be higher compared with the standard requirement.