Simulation of High Voltage Porcelain Bushing under Complicated Working Conditions

Shuhua Yao,Jianli Zhao,Xiao Yang,Jun Hu
DOI: https://doi.org/10.1109/auteee.2018.8720756
2018-01-01
Abstract:Explosive failure of SF6 filled porcelain high voltage bushings is a great threaten to the safe operation of the power system as well as to the security of the neighboring staff and apparatus. Recently, this kind of failure has been reported to occur several times but the reason has not been thoroughly worked out. Thus the operation of the bushing considering various possible occasions under different working conditions requires further investigation. This paper has simulated the electric and thermal distribution for the 500 kV porcelain housed, SF6 filled bushings considering the effect of pollution on the porcelain insulator, the rainy or snowy environment and the liquidation of SF6 under low temperature. The simulation result shows that the external insulation factors such as the pollution and the environment have minor effect on the internal electric field in the bushing. But the liquidation of the SF6 on the inner wall of the porcelain greatly enhances the maximum field strength and may result in insulation failure under specific working condition.