Abstract:30%-40% energy consumption of the HVAC system is caused by chillers. The energy consumption of chillers highly depends on the quality of the operation strategy. A chiller operation strategy based on multiple-objective optimization is proposed in this paper. The strategy consists of three steps: (1) With effectiveness functions, two indicators of the operation goodness, indoor comfort and energy consumption, are quantified to two indicators (2) These two indicators are integrated to one comprehensive indicator. (3) The optimal operation condition is determined by an optimization algorithm to maximize the comprehensive indicator. The parameters in this strategy is defined according to on-site surveys, to improve the application value of the strategy. The effectiveness of the proposed strategy is validated on TRNSYS compared with the 3 common operation strategies adopted in buildings of Shanghai. The simulation results suggest that the proposed strategy is able to save energy of HVAC system with limited loss of indoor comfort. Besides, due to the appropriate arrangement of operation order, the proposed strategy could balance the working time of each chiller to put off the discard of chillers.