Abstract:For central air-conditioning systems, the energy consumption of the chiller plant is huge. By optimizing the operation combination of chillers and the load distribution among chillers, it is possible to realize the energy saving while meeting the cooling demand for end users. Considering that the chiller performance is affected by the cooling capacity, supplying chilled water and returned cooling water temperature, an optimized model-based control strategy of chillers is designed based on the actual performances of chillers. In which, the actual maximum cooling capacity is used as constraint to reduce the search domain and accelerate optimization control calculation speed. Meanwhile, the performances of different optimization algorithms on the optimization results are discussed. Taking a cigarette factory in Wuhan as example to verify the optimized cluster control strategy, the result shows that compared to the traditional control strategy of chiller plant, both traversal optimization and genetic algorithm optimization strategies can achieve an energy-saving rate of about 20% in the entire cooling season.
What problem does this paper attempt to address?