Comparison of Performance Characteristics of Desiccant Coated Air-Water Heat Exchanger with Conventional Air-Water Heat Exchanger – Experimental and Analytical Investigation

X. Y. Sun,Y. J. Dai,T. S. Ge,Y. Zhao,R. Z. Wang
DOI: https://doi.org/10.1016/j.energy.2017.03.078
IF: 9
2017-01-01
Energy
Abstract:In this study, the heat and mass transfer characteristics of desiccant coated heat exchanger (DCHE) and conventional heat exchanger are compared by experiments. A general-purpose test platform is built to test and compare the characteristics above. Based on the designed experimental setup, two heat exchangers of different depths of fins conventional/desiccant coated are experimentally investigated and compared with the given performance evaluation standards. In addition, parametric influences of inlet air velocity, hot water temperature and cycle time are analysed. Experimental results show that compared with the conventional heat exchanger, the heat transfer capacity of DCHE is reduced by 30% because of the heat resistance produced by desiccant coating. Pressure drop and Euler number are both increased by 60% approximately for the same reason. Doubling the depth of fins increases the average moisture removal by 40% and COPth by 10%, without changing the other structure parameters.
What problem does this paper attempt to address?