Performance of desiccant heat exchangers with aluminum foam coated or packed with silica gel

Ramy H. Mohammed,Osama Mesalhy,Mohamed L. Elsayed,Ruiqing Huo,Ming Su,Louis C. Chow
DOI: https://doi.org/10.1016/j.applthermaleng.2019.114626
IF: 6.4
2020-02-01
Applied Thermal Engineering
Abstract:The performance of two types of desiccant silica gel aluminum foam heat exchangers, desiccant packed heat exchanger (DPHE) and desiccant coated heat exchanger (DCHE), are evaluated experimentally and numerically. The DPHE is built by packing an aluminum foam with silica particles, while the DCHE is fabricated by coating silica gel over the ligaments of an aluminum foam. Equilibrium isotherms of the two heat exchangers are measured using the gravimetric approach. An open flow loop setup is constructed to measure the humidity ratio and dry bulb temperature of air upstream and downstream of the desiccant heat exchangers during the humidification and dehumidification process. In addition, the heat and mass transfer mechanism in the two desiccant heat exchangers (DHEs) is investigated using a numerical model. The experimental data obtained are used for the validation of the model, and acceptable agreement is established. The impacts of heat exchanger length and inlet operating conditions on the performance of DPHE and DCHE are investigated.
energy & fuels,engineering, mechanical,thermodynamics,mechanics
What problem does this paper attempt to address?