Experimental Investigation on Cooling Charge Performance of Shell and Tube Type Ice Storage Tank

杜恩杰,吕晓艳,石文星,赵庆珠,刘刚
DOI: https://doi.org/10.3969/j.issn.1005-0329.2004.10.011
2004-01-01
Abstract:The cooling charge performance of shell and tube type ice storage tand was studied. It was showed that the temperature and flow rate of the secondary coolant, and the initial temperature of the water in the tank directly influence the cooling charge performance of the ice storage tank, especially the temperature of the secondary coolant. The cooling charge included two courses, specific cool charge course and potential cool charge course. In the specific cool charge course,the cooling charge speed was comparatively high and in the potential cool charge course,the cooling charge speed was approximately constant and the water is cooled to -2~-1℃ super. It was showed that the tube type ice storage tank has similar cooling charge performance with the conventional external melt ice-on-pipe tank by experimental investigation.