COP Comparison of Refrigeration Cycles with Two-Stage Evaporating Temperatures

LIU Jing-hui,CHEN Jiang-ping,CHEN Zhi-jiu
DOI: https://doi.org/10.3969/j.issn.0255-8297.2006.05.019
2006-01-01
Journal of Applied Sciences
Abstract:This paper presents a mathematical model for theoretical analysis of refrigeration cycles with two-stage evaporating temperatures,and makes a COP comparison between conventional refrigeration cycle with evaporating pressure adjustment valve and 3 cycles with ejectors.The results show that compression/ejection refrigeration cycles can reduce energy loss and improve COP of refrigeration systems.The more the cooling capacity of the high temperature evaporator,the higher the COP can be improved.