Acoustic Signal Characteristics of Corona Discharge in Different Location of GIS

陈隽,刘文浩,卢军,陈敏,李军浩,李彦明
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.12.025
2011-01-01
Abstract:Metal burrs will appear in the high voltage conductor and ground cavity of gas insulated switchgear(GIS) in its manufacture,installation and transportation process.The metal burrs will lead to a corona discharge in operation process and endangering the normal operation of equipments.In order to study the corona partial discharge characteristics of different location in GIS,a 220 kV GIS bus bar cavity is used as a test object.Corona models in GIS are designed,and the partial discharge(PD) signal is obtained based on acoustic method.The experimental results indicate that the PD pattern,attenuation characteristics of signal amplitude and frequency component of acoustic signal have some difference in different location.The corona discharge in ground cavity has smaller amplitude,higher frequency component and severe attenuation than high voltage bar.The study provides experimental reference for PD detection,fault location and pattern recognition on GIS.