Transformer Oil-Paper Insulation Ageing Condition Assessment Using Return Voltage Measurements

PENG Hua-dong,DONG Ming,LIU Yuan,WU Xue-zhou,LI Hong-jie,WANG Chuan-yi
DOI: https://doi.org/10.3969/j.issn.1674-3814.2012.09.002
2012-01-01
Abstract:Aging of oil-paper insulation materials leads to an substantial increase of the water content in the solid insulation and changes of the dielectric response characteristics.If return voltage measurement(RVM) is performed on the ageing insula-tion system,some qualitative features i.e.,higher peak value,greater initial slope and longer peak time can be found.On the basis of the introduction of the basic theory of dielectric resp-onse,some oil-paper samples are measured by RVM under different ageing and moisture states to identify the relationship between the oil-paper insulation ageing condition and RVM.The results show that the dominant time constant decreases significantly when oil-paper insulation gets aged or moistened,and there is a quantitative relationship between the moisture in the solid insulation and the dominant time constant,and the aging condition of the oil-paper insulation can be effectively diagnosed by making use of the dominant time constant.
What problem does this paper attempt to address?