Investigation and Analysis on Energy Efficiency of Air-conditioning Water Chillers in High-rise Complex Office Buildings in Shenzhen

YE Ling,ZHOU Li-jun,JIANG Yi-qiang,YAO Yang
DOI: https://doi.org/10.3969/j.issn.1002-8528.2009.02.010
2009-01-01
Building Science
Abstract:In this paper,the coefficient of performance for refrigeration(COP_e) of air-conditioning water chillers in 28 existing high-rise complex office buildings in Shenzhen was investigated and studied.According to Design Standard for Energy Efficiency of Public Buildings(GB 50189-2005) and The Minimum Allowable Values of the Energy Efficiency and Energy Efficiency Grades for Water Chillers(GB 19577-2004),their design energy efficiency and energy-saving potential were analyzed.It was concluded that more than 20% water chillers should be removed immediately or recently,and energy efficiency level of the rest should be improved.Furthermore,for air-conditioning systems which had been built for more than 10 years with high energy consumption indices,the energy-efficient retrofit on cold source side should be carried out or chillers should be replaced with new ones after comprehensive consideration.