An Improved DC Fault Protection Algorithm for MMC HVDC Grids Based on Modal-Domain Analysis
Saizhao Yang,Wang Xiang,Rui Li,Xiaojun Lu,Wenping Zuo,Jinyu Wen
DOI: https://doi.org/10.1109/jestpe.2019.2945200
IF: 5.462
2020-12-01
IEEE Journal of Emerging and Selected Topics in Power Electronics
Abstract:To detect the dc faults for the modular multilevel converter (MMC)-based dc grids using overhead line transmission, many protection methods in phase-domain have been proposed. These existing protection methods suffer from incomplete function, weak theoretical basis, and sensitivity to fault resistance and noise disturbance. To overcome these shortcomings, this article proposes an improved dc fault protection algorithm using the modal-domain approach for the MMC-based overhead dc grids, which decouples the interaction between positive and negative poles and mitigates the strong frequency dependence of the characteristic impedance in phase-domain. The dc fault equivalent circuits are established in modal-domain and the fault characteristics during the initial stage are analyzed. Based on the modal-domain analysis, the line-mode reactor voltage which combines the fault characteristics of negative and positive reactor voltages is used to identify the internal faults. The zero-mode reactor voltage which enlarges the differences between faulty and healthy poles is used to select the faulted pole. This method is robust to fault resistance and noise with high detection speed. In addition, it is not affected by power reversal, ac faults, and dc circuit breaker (DCCB) operation, which are validated and evaluated by the simulations in PSCAD/EMTDC.
engineering, electrical & electronic