Study on the influence of arrester unit parameters and gap structure on impulse discharge voltage of EGLA

Shu Chen,Jie Guo,Chengbo Hu,Kelun Li,Jun Jia,Yang Xu
DOI: https://doi.org/10.1109/ICPADM.2018.8401107
2018-01-01
Abstract:In order to make the performance of externally gapped line arrester (EGLA) meet the requirements of national standards better, the discharge voltage of its gap becomes the most important parameter so that the study on the relationship between discharge voltage of gap and other factors is considered as a critical project. Generally, before the gap discharging, the distribution of voltage between the gap and the arrester unit is mainly affected by equivalent capacitance. As a result, there is a close relevance between discharge voltage of the gap and the capacitance of arrester unit as well as the gap capacitance. In this paper, capacitances of gaps and voltage distribution in different structures with different arrester unit parameters were calculated under 35kV and 110kV with ANSYS. Experiments under power frequency as well as impulse voltage were conducted on EGLA under different configurations. Results of calculations and experiments were compared and preliminary conclusions were deduced. It indicates that arrester unit parameter and the gap structure affect the discharge voltage of EGLA, and the influence of the former is larger.
What problem does this paper attempt to address?