Characteristic of Power-transmission-induced Current and Power Loss on the OPGW of 750 kV Transmission Line System
Yufei Chen,Yong Wei,Jinxin Cao,Xianchun Wang,Jianguo Wang,Jiaju Zhang,Yadong Fan,Wenzhao Liu
DOI: https://doi.org/10.1016/j.epsr.2024.110130
IF: 3.818
2024-02-03
Electric Power Systems Research
Abstract:The optical fiber composite ground wire (OPGW), serving as a ground wire and providing communication capabilities, has been widely utilized in high-voltage transmission lines in China. Considering the fault current diversion during short circuits and lightning events, OPGW is generally grounded at each tower, while in case of which the induced electromotive force on OPGW generated by the alternating current forms an induced current loop and causes energy losses in the grounding loop. The issue becomes more prominent in higher voltage levels and larger load currents. The assessment of losses before insulating OPGW is crucial data to support the economic consideration and power saving expectation for OPGW insulation retrofit of the overhead power line. To provide a valuable reference and reveal the need for insulation retrofits of the OPGW, this study investigates the induced currents along each tower-grounded OPGW and the corresponding induced power losses on the 750kV double-circuit transmission lines. The impact of various line parameters and operational conditions are discussed via the numerical simulation. The results indicate that the total losses can reach 10 6 kWh/a.km when both circuits are transmitting power at a full load of 2300 MVA. The tower span, tower grounding resistance, and the DC resistance of the OPGW are found to have minimal impact on the total power losses, although the current distribution is affected by these factors. Conductor transposition, phase sequences, and transmission load current have a significant influence on both the amplitude of the induced current and the power losses. Reverse phase sequence ABC-CBA and the symmetrical load on both sides of the circuits could obtain the lowest induced power loss.
engineering, electrical & electronic