Detection Method for DC Arc Based on Electromagnetic Radiation Characteristics

XIONG Qing,XIAO Rong,JI Shengchang,ZHU Lingyu,LIU Yuan,ZHONG Lipeng
DOI: https://doi.org/10.13336/j.1003-6520.hve.20170831026
2017-01-01
Abstract:DC arc is the main cause of system faults since it is hard to extinguish DC arc in DC source systems.Therefore,it is of great significance to find an appropriate method to detect DC arc.A detection method for DC arc based on electromagnetic radiation characteristics is proposed.A DC arc generating device is built to simulate the relaxing connection in DC systems.A fourth-order Hilbert antenna is designed to detect electromagnetic radiation signals of DC arc.The electromagnetic signals of arc are in accordance with the abrupt change of current,and the interval of the abrupt current pulse meets Gamma distribution.The spectra of different abrupt change of current are analyzed.The results indicate that,under the present conditions,the electromagnetic signals have an obvious characteristic frequency (12.9 MHz),and the maximum amplitude frequencies under different circuit current are in a range of 12~14 MHz.The maximum amplitude frequency of DC arc is higher than the frequency when operating switchgear.The interval of DC arc (37 μs) is longer than that of switch operations (7.4 μts).Multiple long duration pulse clusters can be detected when operating switchgears.The results indicate that the characteristic frequency,pulse interval,and pulse clusters duration of electromagnetic radiation signals can be used as the detection parameters of DC arc to identify arc faults.