Fundamental-Frequency Reactive Circulating Current Injection for Capacitor Voltage Balancing in Hybrid-MMC HVDC Systems During Riding Through PTG Faults

Maozeng Lu,Jiabing Hu,Rong Zeng,Zhiyuan He
DOI: https://doi.org/10.1109/tpwrd.2017.2755505
IF: 4.825
2017-01-01
IEEE Transactions on Power Delivery
Abstract:This paper presents a comprehensive analysis and a novel solution for the discharge problem on the half-bridge submodules’ (HBSMs’) capacitors in the hybrid modular multilevel converter (MMC)-based high-voltage direct current transmission systems under a long-term (e.g., several minutes or longer) pole-to-ground fault condition. The mechanism of this issue is analyzed, and then a solution based on fundamental-frequency reactive circulating current (FFRCC) injection is proposed. The influence of FFRCC injection is analyzed in terms of the fluctuated arm capacitor energy and the current stress of semiconductors. Moreover, an enhanced arm voltage modulation method based on HBSMs and full-bridge submodules coordinate control is proposed to accelerate the capacitor voltage balance of HBSMs. Finally, the performance of the proposed control strategy is verified by the simulation results.
What problem does this paper attempt to address?