Experimental Study On The Filtration Efficiency Of Structured Packing Air Handling Processors

Xiaochen Liu,Bowen Guan,Xiaohua Liu
DOI: https://doi.org/10.1016/j.proeng.2015.09.204
2015-01-01
Abstract:Air handling processors with structure packing are widely utilized in the air-conditioning system, in which coupled heat and mass transfer occurs between air and water/desiccant. As an additional benefit, the processor could remove particles at the same time. An experimental setup for a cross-flow packed processor was established to investigate the filtration efficiency, in which air-water and air-desiccant were chosen as flow media. Effects of air and water/desiccant parameters on the filtration performance were experimentally analyzed. The results show that for typical air-to-liquid flow rate ratio (approximate to 1), PM5 arrestance efficiency of packed processor with water is 40%similar to 50% while that with LiBr solution is 20%similar to 30%. The filtration efficiency with LiBr solution is higher than that with water when splash effect of liquid is omitted. (C) 2015 The Authors. Published by Elsevier Ltd.
What problem does this paper attempt to address?