Using Modular Cascade DMC in the Main Steam Temperature Control of Large Power-plant Boiler

李俊,吴刚,孙德敏,张伟康,陈多刚
DOI: https://doi.org/10.3969/j.issn.0253-2778.2003.04.012
2003-01-01
Journal of University of Science and Technology of China
Abstract:In view of the difficulty to put the control loop of main steam temperature in a large powerplant boiler into automatic operating model, such as #1 boiler of Pinwei PowerPlant, the authors acquired a good knowledge of the system characteristics and thought over all the relevant factors. Then, to factors were chosen and modularized cascade dynamic matrix control method was adopted to solve the problem. This method solved the problem perfectly, and its control performance index was bounded in 540±3℃, which was better than the requirement of the national standard. The new control method has the characteristics of online system identification, scrolling optimization and realtime feedback, so it could be used in a system with large time constant, large time delay and multiple disturbances.