CONSTRAINED LOAD FLOW CALCULATION BY SEQUENTIAL QUADRATIC PROGRAMMING METHOD

毕兆东,王建全,韩祯祥
DOI: https://doi.org/10.3321/j.issn:1000-3673.2003.02.008
2003-01-01
Abstract:The constrained load flow is such a power flow which can satisfy all the operation restraints when the network parameter of power system and the load bus data are given and the control variables are preferred. In the paper the constrained load flow is calculated by optimal power flow (OPF) approach in which the sequential quadratic programming (SQP) method is applied, and in the OPF calculation the active power output, the reactive power output and the voltage of generators are selected to be the control variables. The relevant mathematical model and calculation procedure are described and a sensitivity algorithm to deal with Maratos effect is presented. Finally, the calculation results from EPRI 22 bus system and IEEE 118-bus system show that it is effective to apply SQP method to restrained load flow calculation.