Efficient method based on adjoint sensitivity analysis for transient stability constrained optimal power flow

Xiang-yu LIN,Guang-chao GENG,Quan-yuan JIANG
DOI: https://doi.org/10.3969/j.issn.1001-4551.2017.08.020
2017-01-01
Abstract:Aiming at the real-time requirement of online preventive control in modern power system, an efficient method based on adjoint sensitivity analysis for transient stability constrained optimal power flow was proposed. Constraints conversion technology was adopted to re-lieve the curse of dimensionality. A two-layer-structure was proposed to implemented the algorithm:extended approximate Hessian matrix was adopted to improve the accuracy and convergence in optimization layer which was based on predictor-corrector interior point method;in simu-lation layer, adjoint sensitivity analysis was adopted to achieve fast calculation of dynamic sensitivity, and very dishonest Newton method and Jacobian matrix reusing approach were applied to speed up calculation. The results indicate that the proposed approach can significantly im-prove computing efficiency of solving transient stability constrained optimal power flow. Comparison with existing method also shows the great speed advantage of the proposed method, which can meet the requirement of online preventive control in modern power system.
What problem does this paper attempt to address?