Analysis of Inductive Component of Grounding Impedance at Substation

窦鑫,何金良,曾嵘,张波
DOI: https://doi.org/10.3969/j.issn.1001-1609.2004.04.002
2004-01-01
Abstract:The inductive component of substation’s grounding impedance is related to the size of the grounding system,soil resistivity and the injecting point of measuring current.Whether the inductive component should be considered is decided by the scale of the grounding system and soil resistivity.Ordinarily,when the side length of the grounding system exceeds400m,and soil resistivity is smaller than100Ω·m,it should be considered.