Batteries for fast frequency containment response: market impacts on outage dynamics

Christoph Sauer,João Pedro Scherer Cipriani,Gabriel Maier Cocco,Humberto Pinheiro,Martin Wolter
DOI: https://doi.org/10.1515/auto-2024-0099
2024-11-06
at - Automatisierungstechnik
Abstract:Traditional sources like hydro and thermal plants have a well-defined response for inertia and frequency containment during load outages, whereas inverter-interfaced battery systems offer more flexibility as ancillary services. This paper investigates interactions between sources of Frequency Containment Reserve (FCR) after an outage. By integrating a node model, market model, and inverter controller model, the German power plant fleet is simulated, incorporating various energy sources and k-factors. This setup evaluates how different battery participation rates in the FCR market influence system behavior and prices during an outage. The results show that battery storage systems, operating as grid-forming systems like Virtual Synchronous Machines, are particularly efficient for stabilizing frequency due to fast responses. This paper contributes to understanding how battery storage enhances grid stability and market efficiency.
automation & control systems
What problem does this paper attempt to address?