Effect of different air supply parameters on UFAD system performance

wang chenglin,li shuhong,zhang xiaosong,yang wenchao
DOI: https://doi.org/10.3969/j.issn.1001-0505.2015.02.019
2015-01-01
Abstract:In order to obtain the desired air supply parameters in UFAD( underfloor air distribution)system,the orthogonal experiments were employed to investigate the effects of air supply parameters on the distribution of temperature,thermal comfort and indoor air quality. Then,the impacts of the air supply temperature and velocity on the UFAD system performance were studied by using the method of controlling variables. Finally,the preferable air supply parameters which contribute to better thermal stratification,better comfort and low er energy consumption under cooling operating conditions were obtained by Energy Plus energy consumption simulation softw are. The results show that better thermal stratification,thermal comfort and good indoor air quality are achieved with the distance betw een sw irl diffusers and human of 0. 7 m,the air supply temperature of 18 to 20 ℃ and the air supply velocity of 1. 2 to 1. 5 m / s. The simulation results of operation characteristics and energy consumption with different air parameters show that as the air supply parameters are reasonable,the satisfied thermal comfort,thermal stratification and prominent energy saving can be achieved simultaneously with the air supply temperature of 18 ℃ and velocity of 1. 2 m / s.
What problem does this paper attempt to address?