Direct-Current Vacuum Circuit Breaker with Superconducting Fault-Current Limiter

Kun Yang,Yi Yang,Muhammad Junaid,Siyuan Liu,Zhiyuan Liu,Yingsan Geng,Jianhua Wang
DOI: https://doi.org/10.1109/tasc.2017.2767500
IF: 1.9489
2018-01-01
IEEE Transactions on Applied Superconductivity
Abstract:DC circuit breakers based on artificial current zero can interrupt a fault current with a low cost and a fast operation. However, its working reliability is reduced by the charging device of the commutation capacitor which generates the artificial current zero. The objective of this paper is to propose a new topology to avoid the pre-charging process. A resistive type SFCL is used to limit the short circuit current. Meanwhile, the voltage on the quenched SFCL charges the commutation capacitor. The operation sequences are given, and a simulation proved the feasibility. The simulation result shows that the voltage on the SFCL is able to charge the commutation capacitor within a few milliseconds, which is enough to generate an artificial current zero, and then the DC circuit breaker interrupts the fault current successfully.