Research On Current Commutation Measures For Hybrid Dc Circuit Breakers

Weijie Wen,Yulong Huang,Yinshan Sun,Junhui Wu,Mohmmad Al-Dweikat,Weidong Liu
DOI: https://doi.org/10.1109/TPWRD.2016.2535397
IF: 4.825
2016-01-01
IEEE Transactions on Power Delivery
Abstract:The hybrid direct-current circuit breaker (DCCB) consists of a mechanical switch (MS) branch and a static DCCB branch. Once a short-circuit fault is detected, the current should commutate from the MS branch to the static DCCB branch first. In this paper, two current commutation measures have been investigated. A hybrid DCCB prototype with current commutated by the arc voltage of the SF6 switch is developed. Based on the prototype, current commutation and interruption tests have been carried out. The results show the current of 3.4 kA can be commutated-within 2.4 ms, and be interrupted within 6ms. Then, a current commutation drive circuit (CCDC) is proposed as the other current commutation measure. Equivalent current commutation tests have been carried out. The results show with the CCDC, both positive current and negative current can be commutated within tens of microseconds. Using a CCDC in series with a mechanical vacuum switch as the MS branch, a 44 kV/3.4 kA hybrid DCCB prototype is developed. Based on the prototype, current commutation and interruption tests are carried out. According to the results, the current of 3.4 kA can be commutated within 100 mu s, and be interrupted within 2 ms.