Assessment of Voltage Sag Frequency Influenced by Uncertain Influential Factors of Power System
XIAO Xian-yong,LI Wan,MA Chao,YANG Hong-geng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.07.030
2009-01-01
Abstract:Many uncertain factors including generation schema,fault rate and fault location influence the voltage sag frequency.Current stochastic assessment method usually considers that the operation state of generators and fault rate are invariable and the probability distribution rule of system fault is supposed by statistics and experience,so it is not reasonable because the uncertainty of these factors is not considered.Consequently,synthetically considering these factors,the generator operation state was described by generation scheduling and the areas of vulnerability were determined for each generation scheduling.Time-varying fault rate was introduced to describe the fault rate of transmission line and equipment where the weather factor during different time interval was used to determine the fault rate.The probability distribution rule of fault location on transmission line was calculated based on maximum entropy principle without any subjective assumption.In order to testify the rationality of the proposed method,different operating conditions,fault types and weather conditions were considered,by which a new assessment method is presented.Three cases were used for simulation on IEEE 30 standard testing system.The simulation results show that the influence of the uncertain factors is very important to voltage sag assessment,the proposed method is accurate and practical,the assessment results are credible according with the practice,and it is of definite academic value and practical foreground.