Assessment of voltage sag/swell in the distribution network based on energy index and influence degree function
Li Ma,Yu Li,Dingrong Tian,Jinghui Lou,Yingyu Chen,Xin Liu
DOI: https://doi.org/10.1016/j.epsr.2022.109072
IF: 3.818
2022-12-14
Electric Power Systems Research
Abstract:The assessment of voltage sag/swell provides an important basis for the selection of treatment schemes for sensitive equipment. A method for line assessment and sensitive load location selection is proposed to alleviate voltage sag/swell on sensitive loads. The voltage amplitude matrix and duration matrix of voltage sag/swell caused by four types of short-circuit faults on lines are established. For the grid side, the voltage swell energy index is proposed. The voltage sag/swell energy index matrices are determined, and then the pivotal line assessment indicators based on energy index from the grid side and the fragile bus assessment indicators are proposed. For the load side, the voltage swell influence degree function is proposed. The voltage sag/swell influence degree matrices are determined, and then the pivotal line assessment indicators based on influence degree function from the load side are proposed. The proposed indicators are verified in the modified IEEE 30-bus system, and the simulation results show that these indicators can evaluate lines and buses more comprehensively and reasonably, thus providing strategic guidance for the transformation and governance of lines and the selection of the access bus for sensitive loads.
engineering, electrical & electronic