Factors Impacting Self-healing Overvoltage of Smart Distribution Network Connected with Microgrids

Jun HU,Jingwen CAI,Jinliang HE,Ruobing ZHANG,Yu YIN
DOI: https://doi.org/10.13336/j.1003-6520.hve.2014.05.037
2014-01-01
Abstract:In order to investigate the regularity of self-healing overvoltage in smart distribution network that connected with microgrids and affected by different factors, especially the overvoltage in short-circuited network, we established a model of smart distribution network connected with microgrids. Furthermore, taking a position, a type of short circuit fault, and the respective self-healing process as the samples, we analyzed influential factors on overvoltage such as microgrid scale, distribution network scale, and cable length in distribution network, respectively. The simulation indicates that the maximum overvoltage of model system increases with the scale of microgrid, decreases with increasing scale of distribution network, and firstly decreases then increases when the cable length increases. These results can be used for references in specified overvoltage protecting designs of practical smart distribution network connected with microgrids.
What problem does this paper attempt to address?