Effect of low temperature on the performance of a gravity flow CANON-like pilot plant MBR treating surface water

zhaozhi wang,fangshu qu,heng liang,guibai li,robert w field
DOI: https://doi.org/10.1080/19443994.2014.966532
IF: 1.1
2015-01-01
Desalination and Water Treatment
Abstract:A gravity flow completely autotrophic nitrogen removal over nitrite (CANON)-like pilot plant Membrane bio-reactor was designed to treat surface water for indirect potable reuse and was operated for over sevenmonths with a constant Trans-membrane pressure of 100mbar after the start-up phase. The effect of low temperature on the performance of autotrophic nitrogen removal over nitrite was investigated over a seven-month period during which the feed water temperature changed from 29 degrees C to 1 degrees C and the viscosity of the permeate more than doubled. The process showed good biostability and sustainability across the different seasons. Initially when the temperature fell below 10 degrees C (which seems like a turning point for the activity of ANAMMOX bacteria) high fluctuations happened, but the activity of ANAMMOX bacteria recovered in 18d. Increasing Hydrogen retention time during this period was the means by which one can successfully compensate for low temperature. The dissolved oxygen (DO) (7.12-10.9mg/L) in the raw water supported the partial nitrification and anaerobic ammonium oxidation (ANAMMOX) process without the use of aeration. There was high ammonium (up to 5mg/L) removal even at extremely low temperatures of 1 degrees C.
What problem does this paper attempt to address?