Transient Interaction of HVAC and HVDC in Converterer Station in HVDC,Ⅰ:Electromagnetic Transient Model of Equipments in DC Side
CHEN Shui-ming,YU Zhan-qing,XIE Hai-bin,HUANG Lu-lu
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.02.024
2011-01-01
Abstract:Huge interconnected power grids are formed in AC and DC power systems in China.The nanoseconds,microseconds,milliseconds electromagnetic transient due to AC and DC system operation and fault,the DC converter valve movement,the load generated by changes interact in the AC and DC interconnected system,impairing AC and DC power systems,especially leading to the commutation of DC system failures and atresia such serious incidents.Consequently,a theoretical analysis was combined with a test method to establish an over ground network,considering DC electrical networks,control systems and underground grounding system of the full-wave process of the UHV system,Finally,converter transformer was modeled with UMEC model,and transmission line was modeled with J-Marti frequency dependent model;moreover,valve was modeled with transistor,RLC circuit,and other units including DC controller,and DC filter and AC filter were modeled with RLC circuit.The broadband characteristics of electromagnetic transient models of key units in DC sides for the analysis of AC and DC interconnected system were also analyzed.