Resonance Issues and Active Damping in HVAC Grid-Connected Offshore Wind Farm

Shuai Jiang,Shao Zhang,Xi Lu,Baoming GE,Fang Z. Peng
DOI: https://doi.org/10.1109/ecce.2013.6646702
2013-01-01
Abstract:This paper investigates the resonance issues occurring in an HVAC grid-connected offshore wind farm and then presents an active damping control strategy accordingly. The offshore wind farm composed of wind turbine generators, voltage source converters, step-up transformers and HVAC submarine cables is considered in this study. The entire system is modeled by per unit values and emulated by a scaled-down 120Vac singlephase system. A lumped LC network is adopted to model the high-frequency characteristics of the HVAC undersea cable. A systematic analysis based on the frequency-domain approach is carried out. According to the study, the key parameters of system passive components that affect high-frequency resonances are identified. A notch filter based active damping control strategy is then proposed to stabilize the closed-loop system. A prototype composed of a single-phase inverter with filter and a lumped LC network is built in the laboratory and connected to the 120Vac grid. Experimental tests are carried out to validate the theoretical analysis as well as the proposed active damping method.