An Adaptive Distance Relaying Algorithm with A Morphological Fault Detector Embedded

Z. Lu,T. Y. Ji,Q. H. Wu,J. Fitch
DOI: https://doi.org/10.1109/pes.2009.5275579
2009-01-01
Abstract:This paper presents an adaptive distance relaying algorithm (ADRA) for transmission line protection. In ADRA, a fault detector designed based on mathematical morphology (MM) is used to determine the occurrence of a fault. The Euclidean norm of the detector output is then calculated for fault phase selection and fault type classification. With respect to a specific type of fault scenario, an instantaneous circuit model applicable to a transient fault process is constructed to determine the position of the fault. The distance between the fault position and the relay is calculated by a differential equation of the instantaneous circuit model which is resolved in a recursive manner within each sampling interval. Due to the feature of recursive calculation, the protection zone of the relay varies from a small length to large, which increases as an augment in the sample window length. ADRA is evaluated on a transmission model based on PSCAD/EMDTC, under a variety of different fault distances, fault types, fault resistances and loading angles, respectively. The simulation results show that in comparison with conventional DFT-based protection methods, by which the fault distance is calculated using phasor measurements of voltage and current signals in a fixed-length window, ADRA requires much fewer samples to achieve a same degree of the accuracy of fault distance calculation, which enables much faster tripping, and its protection zone can be extended as more samples are used.
What problem does this paper attempt to address?