Developing a Voltage-Stability-Constrained Security Assessment System Part I: Determination of Power System Voltage Security Operation Limits

n c chang,j f su,z b du,l b shi,h f zhou,peter t c tam,y x ni,felix f wu
DOI: https://doi.org/10.1109/TDC.2005.1547128
2005-01-01
Abstract:The method for determining the voltage security operation limits in a practical voltage security analysis (VSA) system based on VSAT software for large power systems is introduced in this paper. These operation limits include bus voltage limits, branch/corridor transfer power limits and P-load limit of the whole system. The voltage security operation limits are determined by the most critical contingency among the studied contingency set. The most critical contingency determines the P-load limit of the whole system, and all kinds of operation parameter limits are operation parameter values corresponding to this P-load limit under pre-contingency. An operation parameter limit is upper limit if the function relationship between this operation parameter and load power is an increasing curve, or lower limit if the function relationship between this operation parameter and load power is an decreasing curve. These operation parameter limits are helpful for operators to monitor the system operation state. The operation limits gotten by VSC-SAS can be visualized for operators to monitor power system operation state and know how far the current operation state is from voltage stability boundary. It is obvious that this kind of information is significant for the operator to avoid voltage instability and collapse. In addition to VSC, line power thermal limits and generator capacity limits etc. should also be considered. The security criteria can be N-1 or possible N-2 contingencies. The fundamental physical concept and calculation in determination of system operation limits is the key issue, which is presented below. The overall structure of the developed VSC-SAS is as the following figure.
What problem does this paper attempt to address?