Small-disturbance voltage stability analysis with EEAC method

Xu Taishan,Yusheng Xue,Han Zhenxiang
1996-01-01
Abstract:A brand-new method for small-disturbance voltage stability assessment (SVSA) is put forth in the present paper, which is based on the natural links between small-disturbance and large-disturbance stabilities, and based on the adaptation of the extended equal area criterion (EEAC) for small-disturbance. A rigorous margin for SVSA is proposed, and is adapted to calculate the maximum loading point. The robustness and rapidity have been verified on the 31 bus Huazhong system and 39 bus New England system.
What problem does this paper attempt to address?