Design of grounding system for wind-photovoltaic-energy storage Hybrid power station

cheng lin,wang sen,li zhizhong,wang jing,zhang bo,shi weidong
DOI: https://doi.org/10.1109/ICHVE.2014.7035509
2014-01-01
Abstract:Based on the Chinese demonstration project of Zhangbei wind-photovoltaic-energy storage (W-PV-ES) hybrid generation, which is the world's biggest and Chinese first new energy utilization platform, the design of grounding system for W-PV-ES Hybrid power station was studied in this paper. Firstly according to the soil resistivity of that power station, measured by the Wenner four-electrode method, the soil constitution, that is three-level layer in summer and is four-level layer including an 1.5m high and 2000Ω·m permafrost in winter, was got, and grounding grid models of W-PV-ES hybrid generation was studied. Then grounding system of that W-PV-ES station was designed, that was the single wind turbine uses concentric bicyclic earth electrode, whose radius are 7m and 10m, and the PV-ES power station uses one horizontal earth electrode every 10m in one direction, every 50m in another direction, and there are 2.5m long vertical grounding rods every 10m around the PV-ES station. For the substation, we adopt the horizontal grounding grid with a 10m interval between conductors and 0.8m burial depth. On the condition that earth current is 10KA, the earth's surface potential, contact potential, and step potential were simulated. After that safety of 35kV system and secondary system were analyzed, when there was short trouble. Finally influence on earth resistance by different grounding materials was studied, galvanized flat steel and copper material was presented as two kinds of selection schemes of grounding materials for considering economic considerations.
What problem does this paper attempt to address?