Analyses of optimal allocation scheme for speed ratio of parallel variable speed pump in heating and air-conditioning system

MA Liang-dong
2011-01-01
Abstract:Correlation model of head,efficiency and power in connection with flow and speed for variable speed pump in heating and air-conditioning system was built.According to the operation characteristics of parallel pumps,the optimal allocation situation of speed ratio of parallel pumps when total pump power attains its lowest level was theoretically analyzed with reference of flow of best efficiency point and speed ratio range.Based on a series of parallel pump operating conditions in a typical variable water flow air-conditiong system with variable differential pressure setpoint control,pump energy saving potential was evaluated by simulation under four control strategies,including one pump running at full speed and another pump running at variable speed,two pumps running at variable speed with 0.05 speed ratio difference,0.1 speed ratio difference and the same speed ratio,respectively.Theoretical analyses and simulation results show that the speed ratio difference leads to extremely low efficiency of one pump or several pumps.It is concluded that the operation strategy with parallel pump running at the same speed ratio is the optimal choice to attain maximum pump saving potential.