Experimental and Numerical Study of Ceiling Jet Fire in a Confined Reduced-scale Corridor

S. Li,Z. Yan,R. Zong,B. Sundén,G. Liao
DOI: https://doi.org/10.3801/iaffs.fss.10-1289
2011-01-01
Fire Safety Science
Abstract:Safety evaluation and assessment becomes an important topic in the design and operation of tunnels and other underground corridors nowadays.The computational fluid dynamics (CFD) model is an indispensable tool in this process, which can predict the possible fire scenarios by calculating the temperature, concentration, velocity and heat transfer in the domain of concern.In this paper, a validation study for a newly developed CFD code SIMTEC is presented, and the modeling results are compared with experimental data which were obtained through a batch of fire tests in a reduced-scale corridor.The simulations agree reasonably well with measured results.In general, the CFD model predicts the hot layer temperature and CO 2 concentration with good accuracy, especially at the position closer to the end of the corridor.The CO concentration close to the fire source is also well captured in the simulation.However, the CO concentration prediction downstream, far away from fire source, is poor.In this study, the effect of corridor fire intensity was also investigated, by varying the fire source size while with other parameters fixed.Both the measurements and the simulation indicate that the average hot layer temperature near the fire source did not change obviously despite the increase in the fire source size.
What problem does this paper attempt to address?